搜索
您的当前位置:首页正文

ALD报警处理

2024-02-05 来源:易榕旅网
ContentsBackChapter 9

0BFAULT SIGNALS

9 FAULT SIGNALS

This chapter comprises the description of the fault signals of the Silicon Crystallisation Unit SCU 400.

Therefore it is necessary that operating and service personnel must read and understand this description before any action is actually carried out.

CONTENTS Page 9 FAULT SIGNALS...................................................................................................1 9.1 GENERAL............................................................................................................2 9.2 INDICATING OF FAULTS....................................................................................2 9.3 ELIMINATING OF FAULT CAUSES....................................................................2 9.4 FAULT NUMBERS...............................................................................................3

sk/32.ExAnlGB/1207-1 1 / 93

Chapter 9

0BFAULT SIGNALS

9.1 General

All plant components or plant-functions which are necessary or indispensable for the process are supervised by the PLC system.

9.2 Indicating of Faults

Malfunctions are indicated visually and audibly on occurrence.

Whenever a fault comes up, a horn sounds and a red flashlight is flashing.

Each furnace is equipped with a RESET button at control cabinets. After taking notice of a fault signal the operator can cancel the horn sound by pressing the RESET button. Furthermore alarm messages are displayed in the belonging OIP-system and must be confirmed in the system.

The ALARM box visible on all Process Pictures shows the number of actual faults. Double click on the box leads to the ALARM MESSAGE window. Here only active alarms are visible.

In the ALARM HISTORY window active and gone alarms are listed.

9.3 Eliminating of Fault Causes

Eliminating of fault causes are only allowed by trained personnel. Work with electricity must be carried out by specially trained and qualified personnel like electricians. ORDER – READ THE INSTRUCTIONS

Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

ORDER - SWITCH OFF THE VOLTAGE SUPPLY If work at or near electrical devices or the melting devices are necessary, switch off the voltage supply at the main switch.

ORDER – WEAR PROTECTIVE EQUIPMENT

Wear the necessary protective equipment like hard hats, protective shoes, dust mask and goggles.

sk/32.ExAnlGB/1207-1 2 / 93

ContentsBackChapter 9

0BFAULT SIGNALS

9.4

Fault Numbers

Page

# Designation

2040 2039 2033 2011 2010 2029 2012 2034 2035 2036 2037 2038 2001 2025 2028 2006 2026 2027 2002 2003 2005 2004 2008 2094 2086 2007 2042 2022 2021 2045 2013 2017 2023 2018

FSAL117 WATERFLOW VACUUM PUMPS FAULT.........................................6 FSAL116 WATERFLOW CHAMBER LID FAULT.............................................7 PSAL101 COOLING WATER PRESSURE FAULT..........................................8 UPS ALARM BATTERY NOT READY..............................................................9 UPS ON BATTERY OPERATION MAIN SUPPLY FAULT...............................10 LEAKTEST FAILED..........................................................................................11 EMERGENCY VENTING ACTIVE.....................................................................12 FSAL111 WATERFLOW POWER CABLES TOP HEATER FAULT..............13 FSAL112 WATERFLOW POWER CABLES BOTTOM HEATER FAULT.......14 FSAL113 WATERFLOW TOP FLANGE FAULT FURNACE LID....................15 FSAL114 WATERFLOW HEAT SINK FAULT.................................................16 FSAL115 WATERFLOW CHAMBER BOTTOM AND WALLS FAULT...........17 DC 24 V FUSES TRIPPED...............................................................................18 LSAH827 SENSOR WATER IN FURNACE ALARM........................................19 M801 HEAT GATE DRIVE SAFETY LIMIT SWITCH AKTIVATED................20 EMERGENCY STOP ACTUATED....................................................................22 M801 VARIABLE FREQUENCY DRIVE FAULT.............................................23 M810 VARIABLE FREQUENCY DRIVE FAULT.............................................24 AC 230 V FUSES TRIPPED.............................................................................25 CIRCUIT BREAKER TRANSFORMER CONTROL VOLTAGE TRIPPED.......26 CIRCUIT BREAKER CABINET COOLING UNIT FAULT.................................27 CABINET COOLING UNIT FAULT...................................................................28 P001 OVERTEMPERATURE............................................................................29 A821 EARTH LEAK TRANSFORMER BOTTOM HEATER............................30 A811 EARTH LEAK TRANSFORMER TOP HEATER...................................31 PSAL009 COMPRESSED AIR SUPPLY PRESSURE LOW...........................32 PSAL205 ARGON SUPPLY PRESSURE LOW...............................................33 TIC821 BOTTOM PYROMETER 821 NO SIGNAL..........................................34 TIC811 TOP PYROMETER 811 NO SIGNAL..................................................35 GS815 CHAMBER LID NOT CLOSED DURING PROCESS...........................36 PROFIBUS SLAVE NO.3 TERMINAL BOX+N3 FAULT..................................37 TIS819 TC TOP HEATING MAXIMAL VALUE ALARM..................................38 TIC811 TOP PYROMETER 811 MAXIMAL VALUE ALARM...........................39 TIS829 TC BOTTOM HEATING MAXIMAL VALUE ALARM..........................40

3 / 93

sk/32.ExAnlGB/1207-1

Chapter 9

0BFAULT SIGNALS

2018 TIC821 BOTTOM PYROMETER 829 MAXIMAL VALUE ALARM...................41 2019 TIS819 TC TOP HEATING SENSOR FAULT...................................................42 2020 TIS829 TC BOTTOM HEATING SENSOR FAULT..........................................43 2081 PROFIBUS SLAVE NO.7 THYRO-P E811 TOP HEATER FAULT..................44 2082 A811 THYRO-P LINE OVERVOLTAGE..........................................................45 2083 A811 THYRO-P LINE UNDERVOLTAGE........................................................46 2084 A811 THYRO-P OVERTEMPERATURE..........................................................47 2085 A811 THYRO-P POWER DEVIATION.............................................................48 2087 A811 TRANSFORMER SECONDARY WINDING TEMPERATURE>70°C.....49 2088 A811 TRANSFORMER PRIMARY WINDING TEMPERATURE>150°C..........50 2089 PROFIBUS SLAVE NO.8 THYRO-P E821 BOTTOM HEATER FAULT..........52 2090 A821 THYRO-P LINE OVERVOLTAGE..........................................................53 2091 E8002 THYRO-P LINE UNDERVOLTAGE.......................................................54 2092 A821 THYRO-P OVERTEMPERATURE..........................................................55 2093 E0002 THYRO-P POWER DEVIATION...........................................................56 2095 A821 TRANSFORMER SECONDARY WINDING TEMPERATURE>70°C.....57 2096 A821 TRANSFORMER PRIMARY WINDING TEMPERATURE>150°C..........58 2097 PIS011 WARNING VACCUM DUST FILTER SHOULD BE CLEANED...........59 2098 PIS011 ALARM VACUUM DUSTST FILTER MUST BE CLEANED................60 2113 AUTO SWITCHING TO MELTING HOLDING PHASE WILL BE IN XXX

MINUTES..............................................................................................................61 2114 AUTO SWITCHING TO CRYSTALLIZING PHASE WILL BE IN XXX MINUTES62 2115 CRUCIBLE CRYSTALLISATION FINISHED...................................................63 2119 AUTO SWITCHING TO CRISTALLIZING HOLDING PHASE WILL BE IN XX

MINUTES..............................................................................................................64 2120 AUTO SWITCHING TO ANNEALING PHASE WILL BE IN XX MINUTES......65 2139 P001 INTERLOCK FAULT...............................................................................66 2137 P001 OVERCURRENT CIRCUIT BREAKER FAULT......................................67 2138 P001 FEEDBACK FAULT................................................................................68 2142 P002 INTERLOCKED FAULT..........................................................................69 2140 P002 OVERCURRENT CIRCUIT BREAKER FAULT......................................70 2146 M810 INTERLOCK FAULT..............................................................................71 2145 M810 OVERCURRENT CIRCUIT BREAKER FAULT.....................................72 2131 E811 INTERLOCKED FAULT..........................................................................73 2129 E811 TOP HEATER OVERCURRENT FAULT................................................74 2130 E811 FEEDBACK FAULT................................................................................75 2134 E821 INTERLOCKED FAULT..........................................................................76 2132 E821 BOTTOM HEATER OVERCURRENT FAULT........................................77

sk/32.ExAnlGB/1207-1 4 / 93

Chapter 9

0BFAULT SIGNALS

2133 2148 2147 2162 2161 2163 2163 2166 2165 2167 2167 2172 2171 2174 2173 E821 FEEDBACK FAULT................................................................................78 M801 INTERLOCK FAULT..............................................................................79 M801 OVERCURRENT CIRCUIT BREAKER FAULT.....................................80 V001 INTERLOCK FAULT...............................................................................81 V001 FEEDBACK FAULT................................................................................82 V003 INTERLOCK FAULT...............................................................................83 V003 FEEDBACK FAULT................................................................................84 V007 INTERLOCK FAULT...............................................................................85 V007 FEEDBACK FAULT................................................................................86 V205 INTERLOCK FAULT...............................................................................87 V205 FEEDBACK FAULT................................................................................88 VP223 INTERLOCK FAULT............................................................................89 VP223 FEEDBACK FAULT.............................................................................90 VP225 INTERLOCK FAULT............................................................................91 VP225 FEEDBACK FAULT.............................................................................92

sk/32.ExAnlGB/1207-1 5 / 93

Chapter 9

0BFAULT SIGNALS

2040

FSAL117 WATERFLOW VACUUM PUMPS FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet HM117 closed Manual valve outlet HM127 closed Flow sensor defect

Signal: Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL FSAL1038 RED Audible: ALARM HORN

Effect on Process Operation:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

To do Option for Operator:

Check water flow and water pressure at water distribution system (should be 5 l/min and > 1,5 bar)

open manual valves of chamber side circuit

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 6 / 93

Chapter 9

0BFAULT SIGNALS

2039

FSAL116 WATERFLOW CHAMBER LID FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM114 closed Manual valve outlet VM124 closed

Flow sensor defect

Signal: Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL FSAL116 RED Audible: ALARM HORN

Effect:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water flow and water pressure, open valve should be 30l/min and > 1,5 bar

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 7 / 93

Chapter 9

0BFAULT SIGNALS

2033

PSAL101 COOLING WATER PRESSURE FAULT

Cause:

Water pressure at water distribution system too low Manual valve inlet VM101 closed Filter is soiled

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL PSAL101 RED Audible: ALARM HORN

Reaction:

All heaters (top heater, bottom heater) shut off automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water pressure, open valve, clean filter (should be > 3,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Top heater E811 switch on automatically Bottom heater E821 switch on automatically

sk/32.ExAnlGB/1207-1 8 / 93

Chapter 9

0BFAULT SIGNALS

2011

UPS ALARM BATTERY NOT READY

Cause:

Unbreakable Power Supply out of duty

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check Battery and fuse at UPS

Press QUIT button and RESET button (for 6 s) to reset alarm

sk/32.ExAnlGB/1207-1 9 / 93

Chapter 9

0BFAULT SIGNALS

2010

UPS ON BATTERY OPERATION MAIN SUPPLY FAULT

Cause:

STOP Power supply for UPS out of operation or overload. Main supply lost

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check STOP Power supply ahead of UPS Check main supply

Press QUIT button and RESET button (for 6 s) to reset alarm

sk/32.ExAnlGB/1207-1 10 / 93

Chapter 9

0BFAULT SIGNALS

2029

LEAKTEST FAILED

Actual Leak rate Exceeds Preset Leak rate in Picture PROCESS Cause:

Evaporation of moisture from silicon and insulation after loading Open or untight flange Untight vacuum seal Open or untight valve

Water leak inside the furnace

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: PROCESS SYMBOL LEAKTEST RED Audible: ALARM HORN

Reaction:

Process will stop in step Leak test until Operator restarts the leak test and preset values for leak test are fulfilled

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION Ignoring leak test failure can result in bad product quality and danger for safety due to high leak rate. The furnace should not be operated further until a plausible reason for the high leak rate is found and the problem is fixed.

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

If leak test can not be passed after several runs (leak rate > 2,0 mbar l/s) check for open flanges, valves, defective seals.

If leak test can not be performed by these measures stop process and check for e.g. water leaks inside furnace.

Reaction of PLC after Alarm Reset:

Automatic Process proceeds further in next step Inertisation after performed leak test

sk/32.ExAnlGB/1207-1 11 / 93

Chapter 9

0BFAULT SIGNALS

2012

EMERGENCY VENTING ACTIVE

Cause:

Yellow push button at control desk is activated by operator

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL VP 205 YELLOW Audible: ALARM HORN

Reaction:

Vacuum valve V001 is closed

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING Injury or plant damage! In case of emergency (water leak during process, silicon run-out) do not stop Emergency venting. Step away from furnace area and take care for good ventilation of the area.

Option for Operator:

Check emergency venting button

If there is no emergency case release emergency venting button Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Vacuum valve V001 can be opened automatically

sk/32.ExAnlGB/1207-1 12 / 93

Chapter 9

0BFAULT SIGNALS

2034

FSAL111 WATERFLOW POWER CABLES TOP HEATER FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM111 closed Manual valve outlet VM121 closed Flow sensor set point maladjusted Flow sensor defect

Signal: Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL FSAL111 RED Audible: ALARM HORN

Reaction:

Top heater is shut off automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water flow and water pressure, open valve, adjust water flow (should be 15 l/min and > 3,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

If green digits on water flow sensor exceed min. set point top heater A811 switched on automatically

sk/32.ExAnlGB/1207-1 13 / 93

Chapter 9

0BFAULT SIGNALS

2035

FSAL112 WATERFLOW POWER CABLES BOTTOM HEATER FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM112 closed Manual valve outlet VM122 closed Flow sensor set point maladjusted Flow sensor defect

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOLS FSAL112 RED Audible: ALARM HORN

Reaction:

Bottom heater is shut off automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water flow and water pressure, open valve, adjust water flow (should be 15l/min and > 3,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

If green digits on water flow sensor exceed min. set point bottom heater A821 switches on automatically

sk/32.ExAnlGB/1207-1 14 / 93

Chapter 9

0BFAULT SIGNALS

2036

FSAL113 WATERFLOW TOP FLANGE FAULT FURNACE LID

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM101 closed Manual valve outlet VM102 closed Flow sensor set point maladjusted Flow sensor defect

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOLS FSAL113 Audible: ALARM HORN

Reaction:

??????Bottom heater is shut off automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water flow and water pressure, open valve, adjust water flow (should be 10l/min and > 3,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Bottom heater A821 switches on automatically

sk/32.ExAnlGB/1207-1 15 / 93

Chapter 9

0BFAULT SIGNALS

2037

FSAL114 WATERFLOW HEAT SINK FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM101 closed Manual valve outlet VM102 closed Flow sensor set point maladjusted Flow sensor defect

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL FSAL114 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Option for Operator:

Check water flow and water pressure, open valve (should be 60l/min and > 3,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 16 / 93

Chapter 9

0BFAULT SIGNALS

2038

FSAL115 WATERFLOW CHAMBER BOTTOM AND WALLS FAULT

Cause: Green digits on water flow sensor reached min. set point (now red) Water pressure too low

Manual valve inlet VM115 closed Manual valve outlet VM125 closed Flow sensor set point maladjusted Flow sensor defect

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: WATER SYMBOL FSAL115 RED Audible: ALARM HORN

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION – DAMAGE Faults in the water distribution system can cause severe damage to the plant. Therefore the water distribution system should be checked before and during the run.

Reaction:

All heaters (top heater, bottom heater) shut off automatically

Option for Operator:

Check water flow and water pressure, open valve (should be 40 l/min and >1,5 bar)

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 17 / 93

Chapter 9

0BFAULT SIGNALS

2001

DC 24 V FUSES TRIPPED

Cause:

Broken fuse

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

No current on power plug in control cabinet

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 18 / 93

Chapter 9

0BFAULT SIGNALS

2025

LSAH827 SENSOR WATER IN FURNACE ALARM

Cause:

Water leak inside furnace chamber

When the furnace is hot, a water leak inside the furnace can result in dangerous reactions during which poisonous and explosive gases can be emitted.

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Only warning, heater do not shut off.

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING Injury or plant damage! In case of emergency (water leak during process, silicon run-out) do not stop Emergency venting. Step away from furnace area and take care for good ventilation of the area.

Option for Operator:

Alarm working people around to step away from furnace area Check view glass at sensor for water traces

If traces of water are visible press EMERGENCY VENTING button and step away from furnace area

If no water traces are visible check sensor and wiring

If no obvious and plausible reason can be detected then try to press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 19 / 93

Chapter 9

0BFAULT SIGNALS

2028

M801 HEAT GATE DRIVE SAFETY LIMIT SWITCH AKTIVATED

Cause:

Heat gate moved over intended end position

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Heat stops immediately

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check limit switches G801 and G806 at heat gate Check heat motor drive

Move heat gate manually out of limit switch

Press QUIT button and RESET button (for 6 s) to reset alarm

sk/32.ExAnlGB/1207-1 20 / 93

Chapter 9

0BFAULT SIGNALS

0023 LSAH8028 Sensor Water in Furnace ALARM

Cause:

Water leak inside furnace chamber

When the furnace is hot, a water leak inside the furnace can result in dangerous reactions during which poisonous and explosive gases can be emitted.

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Only warning, heater do not shut off.

Notes on Safety:

ORDER – READ THE INSTRUCTIONS

Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING Injury or plant damage! In case of emergency (water leak during process, silicon run-out) do not stop Emergency venting. Step away from furnace area and take care for good ventilation of the area.

Option for Operator:

Alarm working people around to step away from furnace area Check view glass at sensor for water traces

If traces of water are visible press EMERGENCY VENTING button and step away from furnace area

If no water traces are visible check sensor

If no obvious and plausible reason can be detected then try to press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 21 / 93

Chapter 9

0BFAULT SIGNALS

2006

EMERGENCY STOP ACTUATED

Cause:

Emergency stop button is pushed

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

All heaters (top heater, bottom heater) shut off automatically Vacuum pump shut off

Vacuum valve is closed automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check for reason why EMERGENCY STOP was activated

If sure that there is no danger for personnel and furnace release EMERGENCY STOP button

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 22 / 93

Chapter 9

0BFAULT SIGNALS

2026

M801 VARIABLE FREQUENCY DRIVE FAULT

Cause:

Fault on Variable Frequency Drive of heat gate motor

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL M801 RED Audible: ALARM HORN

Reaction:

Heat gate stops moving

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

CAUTION If heat gate stops during movement in melting or crystallisation step this could result in bad quality and/or crucible break due to temperature differences. Therefore, immediate decision is needed!

Option for Operator:

Check variable frequency drive of heat gate motor

If heat gate stops during movement use hand drive for moving heat gate to desired position

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 23 / 93

Chapter 9

0BFAULT SIGNALS

2027

M810 VARIABLE FREQUENCY DRIVE FAULT

Cause:

Fault on Variable Frequency Drive of chamber lid motor

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL 8005 RED Audible: ALARM HORN

Reaction:

Chamber lid stops moving

Chamber lid cannot be moved by motor drive

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electric devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check variable frequency drive Check chamber lid motor

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 24 / 93

Chapter 9

0BFAULT SIGNALS

2002

AC 230 V FUSES TRIPPED

Cause:

Broken fuse

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

No current on power plug in control cabinet

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 25 / 93

Chapter 9

0BFAULT SIGNALS

2003

CIRCUIT BREAKER TRANSFORMER CONTROL VOLTAGE TRIPPED

Cause:

Circuit breaker of cabinet cooling unit did release

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

No current on power plug in control cabinet

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 26 / 93

Chapter 9

0BFAULT SIGNALS

2005

CIRCUIT BREAKER CABINET COOLING UNIT FAULT

Cause:

Circuit breaker of cabinet cooling unit did release

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

No cooling of control cabinet

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check for short circuit Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 27 / 93

Chapter 9

0BFAULT SIGNALS

2004

CABINET COOLING UNIT FAULT

Cause:

System fault of the cooling unit.

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

No cooling of control cabinet

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electric devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check control display screen and system alalysis Check temperature in control cabinet Open doors of control cabinet

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 28 / 93

Chapter 9

0BFAULT SIGNALS

2008

P001 OVERTEMPERATURE

Cause:

Temperature of vacuum pump P001 is higher than 120°C

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Vacuum pump P001 stops, P002 stops and vacuum valve V001 will be closed

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electric devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check temperature of vacuum pump

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 29 / 93

Chapter 9

0BFAULT SIGNALS

2094

A821 EARTH LEAK TRANSFORMER BOTTOM HEATER

Cause:

Short circuit between ground and heater

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Only warning, operators' decision needed.

Notes on Safety:

This Alarm is an indication that the heater is not OK.

This can be a reaction of a run-out or other serious problems in the furnace

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check volt- and ampere meter at control cabinet for nervous oscillation Check for asymmetry of phases at volt- and ampere meter Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 30 / 93

Chapter 9

0BFAULT SIGNALS

2086

A811 EARTH LEAK TRANSFORMER TOP HEATER

Cause:

Short circuit between top heater and ground

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER RED Audible: ALARM HORN

Reaction:

Only warning, operators' decision needed.

Notes on Safety:

This Alarm is an indication that the heater is not OK.

This can be a reaction of a run-out or other serious problems in the furnace.

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check volt- and ampere meter at control cabinet for nervous oscillation Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Top heater turned on automatically

sk/32.ExAnlGB/1207-1 31 / 93

Chapter 9

0BFAULT SIGNALS

2007

PSAL009 LOW

COMPRESSED AIR SUPPLY PRESSURE

Cause:

Manual valve closed

Compressed air supply off

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL PSAL009 RED Audible: ALARM HORN

Reaction:

Only warning, immediate reaction needed, because valves can not be operated without compressed air

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check compressed air supply Open manual valve

Press QUIT button and RESET button (for 6 s) to reset alarm

sk/32.ExAnlGB/1207-1 32 / 93

Chapter 9

0BFAULT SIGNALS

2042

PSAL205 ARGON SUPPLY PRESSURE LOW

Cause:

Closed connection to argon distribution system Pressure drop due to high mass flow

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL PSAL205 RED Audible: ALARM HORN

Reaction:

Argon venting Valve V205 is locked Argon purge valve 223 is locked

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check for closed manual valves

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Argon venting Valve VP205 ready for operation Argon purge valve VP223 ready for operation

sk/32.ExAnlGB/1207-1 33 / 93

Chapter 9

0BFAULT SIGNALS

2022

TIC821 BOTTOM PYROMETER 821 NO SIGNAL

Cause:

Pyrometer not connected to cable-loose wire

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIC821 RED Audible: ALARM HORN

Reaction:

No signal available

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check connection

If pyrometer No. 821 is used for temperature control then switch over to another pyrometer in picture MELTING

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Signal available for further processing if Pyrometer is correctly connected

sk/32.ExAnlGB/1207-1 34 / 93

Chapter 9

0BFAULT SIGNALS

2021

TIC811 TOP PYROMETER 811 NO SIGNAL

Cause:

Pyrometer not connected Loose wire

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIC811 RED Audible: ALARM HORN

Reaction:

No signal of pyrometer available

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING Incorrect measurements of temperatures - especially those used for temperature control of the process - can lead to serious danger for personnel and plant, e. g. crucible break!

Option for Operator:

Check pyrometer connection

If pyrometer No. 811 is used for temperature control then switch over to another pyrometer in picture MELTING

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Signal available for further processing if pyrometer is correctly connected

sk/32.ExAnlGB/1207-1 35 / 93

Chapter 9

0BFAULT SIGNALS

2045

GS815 CHAMBER LID NOT CLOSED DURING PROCESS

Cause:

Chamber lid is not closed and not down

Signal:

Visual: RED FLASHLIGHT Control Desk Picture:

Audible: ALARM HORN

Reaction: Only alarming

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check the position of the chamber lid and the limit switch

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 36 / 93

Chapter 9

0BFAULT SIGNALS

2013

PROFIBUS SLAVE NO.3 TERMINAL BOX+N3 FAULT

Cause:

PROFIBUS bus connector is loose

No PROFIBUS connection between IM 153 and PLC The Voltage at IM 153 is not 24-26V DC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture:

Audible: ALARM HORN

Reaction:

Only alarming, operator inspection and decision required.

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check PROFIBUS connection

Check the voltage at IM 153, check the fuse F91

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 37 / 93

Chapter 9

0BFAULT SIGNALS

2017

TIS819 TC TOP HEATING MAXIMAL VALUE ALARM

Cause:

Furnace temperature at thermocouple top heater higher than allowed limit Miss measurement of heater controlling temperature

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIS819 RED Audible: ALARM HORN

Reaction:

All heaters shut off until temperature sinks below maximal value

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check recipe

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

All heaters are switched on automatically after temperatures have fallen below maximal limits

sk/32.ExAnlGB/1207-1 38 / 93

Chapter 9

0BFAULT SIGNALS

2023

TIC811 TOP PYROMETER 811 MAXIMAL VALUE ALARM

Cause:

Furnace temperature at melt Pyrometer 811 higher than allowed limit Mismeasurement of heater controlling temperature

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIC811 RED Audible: ALARM HORN

Reaction:

Only alarming, operator inspection and decision required.

Notes on Safety:

Over-temperature can destroy the furnace and cause damage to man and environment. Do not operate the furnace without Thermocouple measurement.

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check temperature for plausibility

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

All heaters are switched on automatically after temperatures have fallen below maximal limits

sk/32.ExAnlGB/1207-1 39 / 93

Chapter 9

0BFAULT SIGNALS

2018

TIS829 TC BOTTOM HEATING MAXIMAL VALUE ALARM

Cause:

Furnace temperature at thermocouple Bottom higher than allowed limit Mismeasurement of heater controlling temperature

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIS829 RED Audible: ALARM HORN

Reaction:

All heaters shut off until temperature sinks below maximal value

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check temperature for plausibility

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

All heaters are switched on automatically after temperatures have fallen below maximal limits

sk/32.ExAnlGB/1207-1 40 / 93

Chapter 9

0BFAULT SIGNALS

2018

TIC821 BOTTOM PYROMETER 829 MAXIMAL VALUE ALARM

Cause:

Furnace temperature at bottom Pyrometer 821 higher than allowed limit Mismeasurement of heater controlling temperature

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIC821 RED Audible: ALARM HORN

Reaction:

Only alarming, operator inspection and decision required.

Notes on Safety:

Over-temperature can destroy the furnace and cause damage to man and environment. Do not operate the furnace without Thermocouple measurement.

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check temperature for plausibility Check pyrometer

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

All heaters are switched on automatically after temperatures have fallen below maximal limits

sk/32.ExAnlGB/1207-1 41 / 93

Chapter 9

0BFAULT SIGNALS

2019

TIS819 TC TOP HEATING SENSOR FAULT

Cause:

Thermocouple not installed

Thermocouple not connected to cable-loose wire

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIS819 RED Audible: ALARM HORN

Reaction:

No signal from thermocouple available

Notes on Safety:

Replace Thermocouple Do not operate the Furnace without Thermocouple measurement.

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check connection Connect loose wire

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Signal from thermocouple available

sk/32.ExAnlGB/1207-1 42 / 93

Chapter 9

0BFAULT SIGNALS

2020

TIS829 TC BOTTOM HEATING SENSOR FAULT

Cause:

Thermocouple Bottom not installed

Thermocouple Bottom not connected to cable-loose wire

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TIS829 RED Audible: ALARM HORN

Reaction:

No signal of Thermocouple available

Notes on Safety:

Replace Thermocouple Do not operate the Furnace without Thermocouple measurement.

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING Incorrect measurements of temperatures - especially those used for temperature control of the process - can lead to serious danger for personnel and plant, e. g. crucible break!

Option for Operator:

Check thermocouple connection

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

Signal available for further processing if thermocouple is correctly connected

sk/32.ExAnlGB/1207-1 43 / 93

Chapter 9

0BFAULT SIGNALS

2081

PROFIBUS SLAVE NO.7 THYRO-P E811 TOP HEATER FAULT

Cause:

No profibus connection between Thyro P and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER E811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check profibus connection

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 44 / 93

Chapter 9

0BFAULT SIGNALS

2082

A811 THYRO-P LINE OVERVOLTAGE

Cause:

High supply voltage for the thyristor controller of the top heater

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check internal fault archive of Thyro-P Check supply voltage.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 45 / 93

Chapter 9

0BFAULT SIGNALS

2083

A811 THYRO-P LINE UNDERVOLTAGE

Cause:

Low supply voltage for the thyristor controller of the top heater

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check internal fault archive of Thyro-P Check supply voltage.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 46 / 93

Chapter 9

0BFAULT SIGNALS

2084

A811 THYRO-P OVERTEMPERATURE

Cause:

Temperature of the thyristor controller of the top heater higher than 80°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check the airflow in the electrical cabinet

Check internal airflow of Thyro-P for blackings and malfunction of the fan Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 47 / 93

Chapter 9

0BFAULT SIGNALS

2085

A811 THYRO-P POWER DEVIATION

Cause:

The difference of the power setpoint and feedback of the thyristor controller is over the limit

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check the RELEASE TOP HEATER POWER Check volt- and ampere meter at control cabinet Check furnace for RUN-OUT

Check heater for shortcuts and arcing.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 48 / 93

Chapter 9

0BFAULT SIGNALS

2087

A811 TRANSFORMER SECONDARY WINDING TEMPERATURE>70°C

Cause:

Secondary winding temperature of the top heater transformer is higher than 70°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check waterflow

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 49 / 93

Chapter 9

0BFAULT SIGNALS

2088

A811 TRANSFORMER PRIMARY WINDING TEMPERATURE>150°C

Cause:

Primary winding temperature of the top heater transformer is higher than 150°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL TOP HEATER A811 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check waterflow

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 50 / 93

Chapter 9

0BFAULT SIGNALS

sk/32.ExAnlGB/1207-1 51 / 93

Chapter 9

0BFAULT SIGNALS

2089

PROFIBUS SLAVE NO.8 THYRO-P E821 BOTTOM HEATER FAULT

Cause:

No PROFIBUS connection between Thyro P and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER E821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check PROFIBUS connection

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 52 / 93

Chapter 9

0BFAULT SIGNALS

2090

A821 THYRO-P LINE OVERVOLTAGE

Cause:

High supply voltage for the thyristor controller of the bottom heater

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check internal fault archive of Thyro-P Check supply voltage.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 53 / 93

Chapter 9

0BFAULT SIGNALS

2091

E8002 THYRO-P LINE UNDERVOLTAGE

Cause:

Low supply voltage for the thyristor controller of the bottom heater

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check internal fault archive of Thyro-P Check supply voltage.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 54 / 93

Chapter 9

0BFAULT SIGNALS

2092

A821 THYRO-P OVERTEMPERATURE

Cause:

Temperature of the thyristor controller of the bottom heater higher than 80°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check the airflow in the electrical cabinet

Check internal airflow of Thyro-P for blackings and malfunction of the fan Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 55 / 93

Chapter 9

0BFAULT SIGNALS

2093

E0002 THYRO-P POWER DEVIATION

Cause:

The difference of the power setpoint and feedback of the thyristor controller is more than the limit

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator:

Check the RELEASE BOTTOM HEATER POWER Check volt- and ampere meter at control cabinet Check furnace for RUN-OUT

Check heater for shortcuts and arcing.

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 56 / 93

Chapter 9

0BFAULT SIGNALS

2095

A821 TRANSFORMER SECONDARY WINDING TEMPERATURE>70°C

Cause:

Secondary winding temperature of the bottom heater transformer is higher than 70°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check waterflow

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 57 / 93

Chapter 9

0BFAULT SIGNALS

2096

A821 TRANSFORMER PRIMARY WINDING TEMPERATURE>150°C

Cause:

Primary winding temperature of the bottom heater transformer is higher than 150°C

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL BOTTOM HEATER A821 RED

Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check waterflow

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 58 / 93

Chapter 9

0BFAULT SIGNALS

2097 PIS011 WARNING VACCUM DUST FILTER SHOULD BE

CLEANED

Cause:

Filter resistance is high.

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Pumptime will be longer.

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Clean or change filter

Reaction of PLC after Alarm Reset:

In next Automatic cycle yellow filter status signal in OIP picture vacuum will switch into green colour.

sk/32.ExAnlGB/1207-1 59 / 93

Chapter 9

0BFAULT SIGNALS

2098

PIS011 ALARM VACUUM DUSTST FILTER MUST BE CLEANED

Cause:

Filter resistance is too high.

Signal:

Visual: RED FLASHLIGHT Audible: ALARM HORN

Reaction:

Pump time will be much longer

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Clean or change filter

Reaction of PLC after Alarm Reset:

In next Automatic cycle red filter status signal in OIP picture vacuum will switch into green colour.

sk/32.ExAnlGB/1207-1 60 / 93

Chapter 9

0BFAULT SIGNALS

2113

AUTO SWITCHING TO MELTING HOLDING PHASE WILL BE IN XXX MINUTES

Cause:

The auto switch melting holding phase will be start in xxx minutes Signal:

Visual: YELLOW LIGHT Audible: ALARM HORN

Reaction:

Only information

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 61 / 93

Chapter 9

0BFAULT SIGNALS

2114

AUTO SWITCHING TO CRYSTALLIZING PHASE WILL BE IN XXX MINUTES

Cause:

The crystallizing phase will be start in xxx minutes

Signal:

Visual: YELLOW LIGHT Audible: ALARM HORN

Reaction:

Only information

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 62 / 93

Chapter 9

0BFAULT SIGNALS

2115

CRUCIBLE CRYSTALLISATION FINISHED

Cause:

Crystallisation at crucible 1 is finished

Signal:

Visual: YELLOW LIGHT Audible: ALARM HORN

Reaction:

Only information

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 63 / 93

Chapter 9

0BFAULT SIGNALS

2119

AUTO SWITCHING TO CRISTALLIZING HOLDING PHASE WILL BE IN XX MINUTES

Cause:

The auto switch crystallizing holding phase will be start in xx minutes Signal:

Visual: YELLOW LIGHT Audible: ALARM HORN

Reaction:

Only information

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 64 / 93

Chapter 9

0BFAULT SIGNALS

2120

AUTO SWITCHING TO ANNEALING PHASE WILL BE IN XX MINUTES

Cause:

The auto switch annealing phase will be start in xx minutes Signal:

Visual: YELLOW LIGHT Audible: ALARM HORN

Reaction:

Only information

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Reaction of PLC after Alarm Reset:

sk/32.ExAnlGB/1207-1 65 / 93

Chapter 9

0BFAULT SIGNALS

2139

P001 INTERLOCK FAULT

Cause:

Vacuum fore pump V001 is locked due to e.g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V001 RED Audible: ALARM HORN

Reaction:

Valve can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Fore pump can be switched on

sk/32.ExAnlGB/1207-1 66 / 93

Chapter 9

0BFAULT SIGNALS

2137

P001 OVERCURRENT CIRCUIT BREAKER FAULT

Cause:

Circuit breaker of vacuum fore pump P001 is active Motor overload of vacuum fore pump P001

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V001 RED Audible: ALARM HORN

Reaction:

Fore pump P001 stops

Vacuum valve melt chamber V001 is closed automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Fore pump can be switched on

sk/32.ExAnlGB/1207-1 67 / 93

Chapter 9

0BFAULT SIGNALS

2138

P001 FEEDBACK FAULT

Cause:

Contactor of P001 is not closing when it should be energised

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL P001 RED Audible: ALARM HORN

Reaction:

PLC can not operate vacuum fore pump P001

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check for pump

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Fore pump can be switched on

sk/32.ExAnlGB/1207-1 68 / 93

Chapter 9

0BFAULT SIGNALS

2142

P002 INTERLOCKED FAULT

Cause:

Vacuum roots pump is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL P002 RED Audible: ALARM HORN

Reaction:

Roots pump can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check for reason if emergency stop is active

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Roots pump can be switched on

sk/32.ExAnlGB/1207-1 69 / 93

Chapter 9

0BFAULT SIGNALS

2140

P002 OVERCURRENT CIRCUIT BREAKER FAULT

Cause:

Circuit breaker of vacuum roots pump did release

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL P002 RED Audible: ALARM HORN

Reaction:

Vacuum roots pump shut-off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Roots pump can be switched on

sk/32.ExAnlGB/1207-1 70 / 93

Chapter 9

0BFAULT SIGNALS

2146

M810 INTERLOCK FAULT

Cause:

Chamber Lid lifting drive M810 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL M810 RED Audible: ALARM HORN

Reaction:

Hydraulic pump can not be operated by PLC

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING - HYDRAULICS

Option for Operator:

Check Chamber lid lifting drive

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Hydraulic pump can be operated by PLC

The hydraulic system is under high pressure.

sk/32.ExAnlGB/1207-1 71 / 93

Chapter 9

0BFAULT SIGNALS

2145

M810 OVERCURRENT CIRCUIT BREAKER FAULT

Cause:

Circuit breaker of chamber lid lifting drive M810 did release Motor overload of lifting device

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL M810 RED Audible: ALARM HORN

Reaction:

Cahmber lid lifting drive shuts off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check circuit breaker

Check temperature of lifting drive

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Hydraulic pump can be operated by PLC

sk/32.ExAnlGB/1207-1 72 / 93

Chapter 9

0BFAULT SIGNALS

2131

E811 INTERLOCKED FAULT

Cause:

Top heater E811 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E811 RED Audible: ALARM HORN

Reaction:

Top heater can not be operated by PLC

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Top heater can not be operated by PLC

sk/32.ExAnlGB/1207-1 73 / 93

Chapter 9

0BFAULT SIGNALS

2129

E811 TOP HEATER OVERCURRENT FAULT

Cause:

Circuit breaker of top heater did release

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E811 RED Audible: ALARM HORN

Reaction:

Top heater shuts off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Top heater is switched on

sk/32.ExAnlGB/1207-1 74 / 93

Chapter 9

0BFAULT SIGNALS

2130

E811 FEEDBACK FAULT

Cause:

Contactor of top heater E811 is not closing when it should be energised.

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E811 RED Audible: ALARM HORN

Reaction:

Top heater shuts off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check release switch at control cabinet +S1

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Top heater is switched on

sk/32.ExAnlGB/1207-1 75 / 93

Chapter 9

0BFAULT SIGNALS

2134

E821 INTERLOCKED FAULT

Cause:

Bottom heater E821 is locked due to e.g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E821 RED Audible: ALARM HORN

Reaction:

Bottom heater shuts off

Bottom heater can not be operated by PLC

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Bottom heater can be operated by PLC

sk/32.ExAnlGB/1207-1 76 / 93

Chapter 9

0BFAULT SIGNALS

2132

E821 BOTTOM HEATER OVERCURRENT FAULT

Cause:

Circuit breaker of bottom heater E821 did release

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E821 RED Audible: ALARM HORN

Reaction:

Bottom heater shuts off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check for short circuit Check fuse

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Bottom heater can be operated by PLC

sk/32.ExAnlGB/1207-1 77 / 93

Chapter 9

0BFAULT SIGNALS

2133

E821 FEEDBACK FAULT

Cause:

Contactor of bottom heater E821 is not closing when it should be energised. PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL E821 RED Audible: ALARM HORN

Reaction:

Bottom heater shuts off

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check release switch at control cabinet +S1

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Bottom heater is switched on

sk/32.ExAnlGB/1207-1 78 / 93

Chapter 9

0BFAULT SIGNALS

2148

M801 INTERLOCK FAULT

Cause:

Motor of heat gate locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL M801 RED Audible: ALARM HORN

Reaction:

Heat gate can not be operated by PLC

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Heat gate can be operated by PLC

sk/32.ExAnlGB/1207-1 79 / 93

Chapter 9

0BFAULT SIGNALS

2147

M801 OVERCURRENT CIRCUIT BREAKER FAULT

Cause:

Circuit breaker of heat gate did release Motor overload of heat gate

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: CHAMBER SYMBOL M801 RED Audible: ALARM HORN

Reaction:

Motor of heat gate is stopped

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

WARNING – HAZARDOUS VOLTAGE Work at electrical devices must be carried out by specially trained and qualified personnel like electricians.

Option for Operator: Check circuit breaker Check for short circuit

Check temperature of motor

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: Heat gate can be operated by PLC

sk/32.ExAnlGB/1207-1 80 / 93

Chapter 9

0BFAULT SIGNALS

2162

V001 INTERLOCK FAULT

Cause:

Vacuum valve melt chamber V001 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V001 RED Audible: ALARM HORN

Reaction:

KP0001 can not be opened automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check conditions

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V001 can be opened

sk/32.ExAnlGB/1207-1 81 / 93

Chapter 9

0BFAULT SIGNALS

2161

V001 FEEDBACK FAULT

Cause:

Vacuum valve melt chamber V001 did not reach limit switch V001 is on manual mode

No communication between valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V001 RED Audible: ALARM HORN

Reaction:

KP0001 can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check valve and limit switches at valve

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V001 will be activated

sk/32.ExAnlGB/1207-1 82 / 93

Chapter 9

0BFAULT SIGNALS

2163

V003 INTERLOCK FAULT

Cause:

Vacuum control valve melt chamber V003 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V003 RED Audible: ALARM HORN

Reaction:

V003 can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check for conditions which must be fulfilled

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V003 will be activated

sk/32.ExAnlGB/1207-1 83 / 93

Chapter 9

0BFAULT SIGNALS

2163

V003 FEEDBACK FAULT

Cause:

Vacuum control valve melt chamber V003 did not reach limit switch V003 is in manual mode

No communication between valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V003 RED Audible: ALARM HORN

Reaction:

V003 can not be operated by PLC

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check Valve

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V003 will be activated

sk/32.ExAnlGB/1207-1 84 / 93

Chapter 9

0BFAULT SIGNALS

2166

V007 INTERLOCK FAULT

Cause:

Atmosphere Vent valve melt chamber V007 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V007 RED Audible: ALARM HORN

Reaction:

V007 can not be activated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Check conditions for interlock

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V007 will be activated

sk/32.ExAnlGB/1207-1 85 / 93

Chapter 9

0BFAULT SIGNALS

2165

V007 FEEDBACK FAULT

Cause:

Atmosphere vent valve melt chamber V007 did not reach limit switch V007 is in manual mode

No communication between valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V007 RED Audible: ALARM HORN

Reaction:

V007 can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check valve

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: V007 will be activated

sk/32.ExAnlGB/1207-1 86 / 93

Chapter 9

0BFAULT SIGNALS

2167

V205 INTERLOCK FAULT

Cause:

Emergency venting Argon Inert gas valve melt chamber V205 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V205 RED Audible: ALARM HORN

Reaction:

V205 can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check conditions

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

V205 will be activated if emergency venting is activated

sk/32.ExAnlGB/1207-1 87 / 93

Chapter 9

0BFAULT SIGNALS

2167

V205 FEEDBACK FAULT

Cause:

No Feedback of emergency venting Argon inert gas valve melt chamber V205 to PLC

Argon-/Inert gas valve V205 did not reach limit switch No communication between Valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL V200 RED Audible: ALARM HORN

Reaction:

V205 can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator: Check valve

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset:

V205 will be activated if emergency venting is activated

sk/32.ExAnlGB/1207-1 88 / 93

Chapter 9

0BFAULT SIGNALS

2172

VP223 INTERLOCK FAULT

Cause:

Argon top and bottom purging shut-off valve VS2023 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL VS223 RED Audible: ALARM HORN

Reaction:

Valve can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: VP223 can be opened

sk/32.ExAnlGB/1207-1 89 / 93

Chapter 9

0BFAULT SIGNALS

2171

VP223 FEEDBACK FAULT

Cause:

Argon top and bottom purging shut-off valve did not reach limit switch Argon top and bottom purging shut-off valve is in manual mode No communication between valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL VS223 RED Audible: ALARM HORN

Reaction:

Valve can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: VP223 will be activated

sk/32.ExAnlGB/1207-1 90 / 93

Chapter 9

0BFAULT SIGNALS

2174

VP225 INTERLOCK FAULT

Cause:

Argon central gas inlet purging shut-off VP225 is locked due to e. g. emergency stop

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL VP225 RED Audible: ALARM HORN

Reaction:

Valve can not be operated automatically

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: VP225 can be opened

sk/32.ExAnlGB/1207-1 91 / 93

Chapter 9

0BFAULT SIGNALS

2173

VP225 FEEDBACK FAULT

Cause:

Central gas inlet shut off valve VP225 did not reach limit switch No communication between valve and PLC

Signal:

Visual: RED FLASHLIGHT Control Desk Picture: VACUUM SYMBOL VP225 RED Audible: ALARM HORN

Reaction:

Notes on Safety:

ORDER – READ THE INSTRUCTIONS Pay attention to the instructions, especially the chapter general safety instructions in these operating instructions!

Option for Operator:

Press QUIT button and RESET button (for 6 s) to reset alarm

Reaction of PLC after Alarm Reset: VP225 will be activated

sk/32.ExAnlGB/1207-1 92 / 93

Chapter 9

0BFAULT SIGNALS

sk/32.ExAnlGB/1207-1 93 / 93

因篇幅问题不能全部显示,请点此查看更多更全内容

Top